Innervegg med enkelt bindingsverk av stål og dobbel gipsplatekledning

I denne løsningen

Gyproc

Kontakt oss om denne løsningen

Felles svill og stender 45 mm

cc-
avstand
Antall lag
og type
gipsplater
Isolasjons-
tykkelse
Lyd 2)Brann-
motstand 1)
Maks
vegghøyde 1)
Vegg-
tykkelse
Veggkode 3)
R'w
mmmmERXRSkillende (EI)ERXRmmER eller XR
450

Gyproc ErgoLite Klima

EE-EE
M036-602650-95**45/45 450 EE-EE M0
M5039-**45/45 450 EE-EE M50
Gyproc Normal Klima
NN-NN
M038-602800-95**45/45 450 NN-NN M0
M5042-**45/45 450 NN-NN M50
Gyproc Protect F Klima
PP-PP
M038-1203000-107**45/45 450 PP-PP M0
M5042-**45/45 450 PP-PP M50
Gyproc Robust Klima
RN-NR
--------
----
Gyproc Habito
HN-NH
M041-903150-95**45/45 450 HN-NH M0
M5045-**45/45 450 HN-NH M50
 
600Gyproc ErgoLite Klima
EE-EE
M037-602350-95**45/45 600 EE-EE M0
M5040-**45/45 600 EE-EE M50
Gyproc Normal Klima
NN-NN
M039-602500-95**45/45 600 NN-NN M0
M5043-**45/45 600 NN-NN M50
Gyproc Protect F Klima
PP-PP
M039-1202700-107**45/45 600 PP-PP M0
M5043-**45/45 600 PP-PP M50

Gyproc Robust Klima
RN-NR
--------
----
Gyproc Habito
HN-NH
M042-902800-95**45/45 600 HN-NH M0
M5046-**45/45 600 HN-NH M50
  1. Maks vegghøyde for en ubelastet vegg bestemmes utfra følgende utbøyningskriterier: 
    u ≤ 10 mm for H ≤ 3m  og  1/300 x H for H > 3 m når veggen belastes av en horisontal linjelast på 0,5 kN/m på midten. 
    Elementer som påvirker maks vegghøyde er stenderdimensjon, stendertype og c/c-avstand i tillegg til platetype og belastning. 
    Se Gyproc Håndbok kap. 4.3.2 for andre vegghøyder og belastninger. For vegger med maks vegghøyde over 6 m og som skal oppfylle brannmotstand må særskilte tiltak gjøres da brannmotstanden gjelder kun opp til 6 m. 

  2. Forventet verdi i ferdig bygning, R'w  - Forventede feltverdier i bygning under normale gode flankeforhold, det vil si med liten lydoverføring utenom selve skillekonstruksjonen. Forventede feltverdier ligger lavere enn de laboratoriemålte verdiene. Høyt presterende vegger vil ha de største forskjellene. El-installasjoner eller gjennomføringer kan redusere konstruksjonens ytelse og er ikke inkludert. 

  3. Stendertype ER (Gyproc Standardstender) eller XR (Gyproc Lydstender) avhengig av valgt system. ** byttes ut med ER eller XR i veggkoden. 

Felles svill og stender 70 mm

cc-
avstand
Antall lag
og type
gipsplater
Isolasjons-
tykkelse
Lyd 2)Brann-
motstand 1)
Maks
vegghøyde 1)
Vegg-
tykkelse
Veggkode 3)
R'w
mmmmERXRSkillende (EI)ERXRmmER eller XR
450

Gyproc ErgoLite Klima

EE-EE
M037396038004050120**70/70 450 EE-EE M0
M704244**70/70 450 EE-EE M70
Gyproc Normal Klima
NN-NN
M040416042504500120**70/70 450 NN-NN M0
M704648**70/70 450 NN-NN M70
Gyproc Protect F Klima
PP-PP
M0404112048005050132**70/70 450 PP-PP M0
M704648**70/70 450 PP-PP M70
Gyproc Robust Klima
RN-NR
M042436049505150120**70/70 450 RN-NR M0
M704849**70/70 450 RN-NR M70
Gyproc Habito
HN-NH
M043449053005450120**70/70 450 HN-NH M0
M704951**70/70 450 HN-NH M70
 
600Gyproc ErgoLite Klima
EE-EE
M038406030503250120**70/70 600 EE-EE M0
M704345**70/70 600 EE-EE M70
Gyproc Normal Klima
NN-NN
M041426035503750120**70/70 600 NN-NN M0
M704748**70/70 600 NN-NN M70
Gyproc Protect F Klima
PP-PP
M0414212039504200132**70/70 600 PP-PP M0
M704748**70/70 600 PP-PP M70

Gyproc Robust Klima
RN-NR
M043446041004300120**70/70 600 RN-NR M0
M704950**70/70 600 RN-NR M70
Gyproc Habito
HN-NH
M044459044504650120**70/70 600 HN-NH M0
M705152**70/70 600 HN-NH M70
  1. Maks vegghøyde for en ubelastet vegg bestemmes utfra følgende utbøyningskriterier: 
    u ≤ 10 mm for H ≤ 3m  og  1/300 x H for H > 3 m når veggen belastes av en horisontal linjelast på 0,5 kN/m på midten. 
    Elementer som påvirker maks vegghøyde er stenderdimensjon, stendertype og c/c-avstand i tillegg til platetype og belastning. 
    Se Gyproc Håndbok kap. 4.3.2 for andre vegghøyder og belastninger. For vegger med maks vegghøyde over 6 m og som skal oppfylle brannmotstand må særskilte tiltak gjøres da brannmotstanden gjelder kun opp til 6 m. 

  2. Forventet verdi i ferdig bygning, R'w  - Forventede feltverdier i bygning under normale gode flankeforhold, det vil si med liten lydoverføring utenom selve skillekonstruksjonen. Forventede feltverdier ligger lavere enn de laboratoriemålte verdiene. Høyt presterende vegger vil ha de største forskjellene. El-installasjoner eller gjennomføringer kan redusere konstruksjonens ytelse og er ikke inkludert. 

  3. Stendertype ER (Gyproc Standardstender) eller XR (Gyproc Lydstender) avhengig av valgt system. ** byttes ut med ER eller XR i veggkoden. 

Felles svill og stender 95 mm

cc-
avstand
Antall lag
og type
gipsplater
Isolasjons-
tykkelse
Lyd 2)Brann-
motstand 1)
Maks
vegghøyde 1)
Vegg-
tykkelse
Veggkode 3)
R'w
mmmmERXRSkillende (EI)ERXRmmER eller XR
450

Gyproc ErgoLite Klima

EE-EE
M038416058006200145**95/95 450 EE-EE M0
M504246**95/95 450 EE-EE M50
M1004448**95/95 450 EE-EE M100
Gyproc Normal Klima
NN-NN
M043456064506800145**95/95 450 NN-NN M0
M504650**95/95 450 NN-NN M50
M1004852**95/95 450 NN-NN M100
Gyproc Protect F Klima
PP-PP
M0434512070007000157**95/95 450 PP-PP M0
M504650**95/95 450 PP-PP M50
M1004852**95/95 450 PP-PP M100
Gyproc Robust Klima
RN-NR
M044466070007000145**95/95 450 RN-NR M0
M504951**95/95 450 RN-NR M50
M1005153**95/95 450 RN-NR M100
Gyproc Habito
HN-NH
M044469070007000145**95/95 450 HN-NH M0
M504951**95/95 450 HN-NH M50
M1005153**95/95 450 HN-NH M100
 
600Gyproc ErgoLite Klima
EE-EE
M039426045504900145**95/95 600 EE-EE M0
M504347**95/95 600 EE-EE M50
M1004549**95/95 600 EE-EE M100
Gyproc Normal Klima
NN-NN
M044466055005800145**95/95 600 NN-NN M0
M504851**95/95 600 NN-NN M50
M1005052**95/95 600 NN-NN M100
Gyproc Protect F Klima
PP-PP
M0444612061506500157**95/95 600 PP-PP M0
M504851**95/95 600 PP-PP M50
M1005052**95/95 600 PP-PP M100

Gyproc Robust Klima
RN-NR
M045476064006700145**95/95 600 RN-NR M0
M505052**95/95 600 RN-NR M50
M1005354**95/95 600 RN-NR M100
Gyproc Habito
HN-NH
M045479068507000145**95/95 600 HN-NH M0
M505052**95/95 600 HN-NH M50
M1005354**95/95 600 HN-NH M100
  1. Maks vegghøyde for en ubelastet vegg bestemmes utfra følgende utbøyningskriterier: 
    u ≤ 10 mm for H ≤ 3m  og  1/300 x H for H > 3 m når veggen belastes av en horisontal linjelast på 0,5 kN/m på midten. 
    Elementer som påvirker maks vegghøyde er stenderdimensjon, stendertype og c/c-avstand i tillegg til platetype og belastning. 
    Se Gyproc Håndbok kap. 4.3.2 for andre vegghøyder og belastninger. For vegger med maks vegghøyde over 6 m og som skal oppfylle brannmotstand må særskilte tiltak gjøres da brannmotstanden gjelder kun opp til 6 m. 

  2. Forventet verdi i ferdig bygning, R'w  - Forventede feltverdier i bygning under normale gode flankeforhold, det vil si med liten lydoverføring utenom selve skillekonstruksjonen. Forventede feltverdier ligger lavere enn de laboratoriemålte verdiene. Høyt presterende vegger vil ha de største forskjellene. El-installasjoner eller gjennomføringer kan redusere konstruksjonens ytelse og er ikke inkludert. 

  3. Stendertype ER (Gyproc Standardstender) eller XR (Gyproc Lydstender) avhengig av valgt system. ** byttes ut med ER eller XR i veggkoden. 

Tabell - Felles svill og stender 120 mm

cc-
avstand
Antall lag
og type
gipsplater
Isolasjons-
tykkelse
Lyd 2)Brann-
motstand 1)
Maks
vegghøyde 1)
Vegg-
tykkelse
Veggkode 3)
R'w
mmmmERXRSkillende (EI)ERXRmmER eller XR
450

Gyproc ErgoLite Klima

EE-EE
M040426070007000170**120/120 450 EE-EE M0
M504448**120/120 450 EE-EE M50
M1004650**120/120 450 EE-EE M100
Gyproc Normal Klima
NN-NN
M043456070007000170**120/120 450 NN-NN M0
M504751**120/120 450 NN-NN M50
M1004952**120/120 450 NN-NN M100
Gyproc Protect F Klima
PP-PP
M0434512070007000182**120/120 450 PP-PP M0
M504751**120/120 450 PP-PP M50
M1004952**120/120 450 PP-PP M100
Gyproc Robust Klima
RN-NR
M045476070007000170**120/120 450 RN-NR M0
M505052**120/120 450 RN-NR M50
M1005153**120/120 450 RN-NR M100
Gyproc Habito
HN-NH
M045479070007000170**120/120 450 HN-NH M0
M505052**120/120 450 HN-NH M50
M1005253**120/120 450 HN-NH M100
 
600Gyproc ErgoLite Klima
EE-EE
M042446063506800170**120/120 600 EE-EE M0
M504649**120/120 600 EE-EE M50
M1004851**120/120 600 EE-EE M100
Gyproc Normal Klima
NN-NN
M045466070007000170**120/120 600 NN-NN M0
M504852**120/120 600 NN-NN M50
M1005153**120/120 600 NN-NN M100
Gyproc Protect F Klima
PP-PP
M0454612070007000182**120/120 600 PP-PP M0
M504951**120/120 600 PP-PP M50
M1005153**120/120 600 PP-PP M100

Gyproc Robust Klima
RN-NR
M046486070007000170**120/120 600 RN-NR M0
M505253**120/120 600 RN-NR M50
M1005354**120/120 600 RN-NR M100
Gyproc Habito
HN-NH
M046489070007000170**120/120 600 HN-NH M0
M505253**120/120 600 HN-NH M50
5354**120/120 600 HN-NH M100
  1. Maks vegghøyde for en ubelastet vegg bestemmes utfra følgende utbøyningskriterier: 
    u ≤ 10 mm for H ≤ 3m  og  1/300 x H for H > 3 m når veggen belastes av en horisontal linjelast på 0,5 kN/m på midten. 
    Elementer som påvirker maks vegghøyde er stenderdimensjon, stendertype og c/c-avstand i tillegg til platetype og belastning. 
    Se Gyproc Håndbok kap. 4.3.2 for andre vegghøyder og belastninger. For vegger med maks vegghøyde over 6 m og som skal oppfylle brannmotstand må særskilte tiltak gjøres da brannmotstanden gjelder kun opp til 6 m. 

  2. Forventet verdi i ferdig bygning, R'w  - Forventede feltverdier i bygning under normale gode flankeforhold, det vil si med liten lydoverføring utenom selve skillekonstruksjonen. Forventede feltverdier ligger lavere enn de laboratoriemålte verdiene. Høyt presterende vegger vil ha de største forskjellene. El-installasjoner eller gjennomføringer kan redusere konstruksjonens ytelse og er ikke inkludert. 

  3. Stendertype ER (Gyproc Standardstender) eller XR (Gyproc Lydstender) avhengig av valgt system. ** byttes ut med ER eller XR i veggkoden. 

Gyproc Innerveggsystem med enkelt bindingsverk av stål og med dobbel gipsplatekledning på hver side

Konstruksjonen er bygd opp av Gyproc stålstendere montert på henholdsvis c/c 450 mm eller c/c 600 mm og kledd med to gipsplatelag på hver side. 

Dokumentasjon relatert til løsningen

Kontakt oss om denne løsningen